DIGITAL TEMPERATURE CONTROLLER

 

11

 

  TYPE DT 72 / DT 96
 ORDER CODE  DT 72:55572  /  DT 96:55596
 GENERAL SPECIFICATIONS  The microcontroller based, digital temperature controller with 3 digits display and memory protection.
 USE OF DEVICE  1) The process temperature value and control method can be indicated and adjusted easily on the digital display.
 2) Control method can be chosen between ON – OFF or Time Proportional 
 3) Memory protection with EEPROM.
 4) Input type is J type (Fe-CuNi) thermocouple.
 5) Relay output.
 6) The control method (HYS-PI) and output state (OUT) can be shown easily by LEDs.
 WORKING DEVICE  Factory Defaults; SET: 200 °C, HYS: 10 °C, TP: 20 s ON-OFF control method;
 If the process temperature is bigger than the desired temperature value, the control output is deenergised. If the process temperature  is smaller than the desired Temperature value, the control output is energized. Time Proportional control method;
 Due to the proportional band which is %2, 4 °C under and over of the desired temperature value, device works as same as ON – OFF  control method. In the other values device works related to the control period. When using these methods, if the energy is cut off,  adjusted values and control method retains.If the “Err” message is seen on the display, it means temperature sensor is disconnected  or over temperature condition is occured. When this message is seen, the control output is deenergised.
 MEASUREMENT AND CONTROL RANGE  J Type: 0 °C…+400 °C
 ACCURACY  ± (%1+1)
 SUPPLY VOLTAGE  230 Vac, ±% 20, 50 / 60 Hz
 POWER CONSUMPTION  < 3 VA
 ELECTRICAL LIFE  300.000 ON / OFF (Resistive Load) 0°C…60°
 OPERATING TEMPERATURE  -5°C…+55°C
 TEMPERATURE COMPANSATION  -5°C…+55°C
 SET VALUE RANGE  J Type: 0 °C…+400 °C
 HYS VALUR RANGE  (for ON – OFF method) 2…20°C
 PROPORTIONAL BAND  %2 (for Time Proportional method)
 CONTROL PERIOD  10 s … 200 s (for Time Proportional method)
 SENSITIVITY  1°C
 CONTROL OUTPUT  SPDT Relay (230 V AC, 3A, Resistive Load)
 ELECTIRICAL CONNECTION  Socketed Connectors
 CONNECTION  Front Panel
 PROTECTION CLASS  Front : IP 54 , Connection : IP 20 , Class II

 

table

 

 Order Code   Type   Temperature Sensor   Display   Weight (kg)   Dimensions 
 55572  DT 72   J / K Type   3 digit 
 red
 10 mm
 0,26  Fig 3
 55596 DT 96  J / K Type  3 digit 
 red
 14 mm
 0,3  Fig 2

 

Categories: KRK